2 8 Loop Panel Fire Alarm Control Panel Standard (TI-002320-ST)
Features:
- Fully expandable from2-8 loops via plug-in loop driver boards
- 20 programmable Zonal / 25 System LEDs with slide-in labels
- Dedicated loop driver to support fully digital communication protocol
- Intelli-Sense graphical LCD user interface and support for up to 200 fire zones by default
- Allowing full EN54 compliance without additional hardware
- Dual flash-based microprocessor technology with real-time clock onboard
- Dedicated USB & RS232 serial port for direct
- PC or modem connection
- Installer friendly Auto-learn, Loop Detection and Onboard Scope facility for ease of
- Commissioning and fault finding
- Fully programmable via the onboard
- Alphanumeric keypad, or PC configuration tools
- The graphical display can be configured to
- operate with virtually any language or character set and allow the installer's logo to
- be applied using the Logo application software
Specifications:
Model: TI-002320-ST
Type: Addressable
Base Technology: Dual flash-based processors with real-time clock, trace diagnostics, programmable languages and character sets
Display: White backlit 240 x 64 graphical LCD
LED Indicators: 22 red (1 x Fire, 1 x More Alarms, 20 x Zonal Programmable), 1 green (Power), 13 amber and 7 bi-colour (Fault & System)
Controls: Alpha numeric keypad permitting Navigation, Reset, Mute, Silence, Resound, Evacuate, and 4 x Programmable Push Buttons Actual 2
Protocol: Fully digital communication protocol
Number of Fire Zones: 2000 (200 per individual panel)
Number of Loops: Dedicated 2-8 loop control panel
Devices per Loop: 240 Addressable Detectors and Devices
Loop Current: 500mA
On-Board Sounder Circuits: 8x1 Amp programmable
On-Board Relays: 4x1Amp 30vAC/DC programmable (10mA,5vmin)-expandable to 8 using 2x TI-002370 (2-Way Relay Card)
Auxiliary Supply: 2 x 24v500mA
Programmable Input: 2 x monitored programmable input on-board
Programmable Key Switch Inputs: 16 volt free digital inputs
Total Available Output Current: 2 x 5A maximum available for loop current + sounder outputs + auxiliary supply
Mains Supply: 200 - 240v 47-63 Hz AC (+10%, -15% tolerance) 1.4Amax
Battery Capacity: 2 x 24V4Ah internal(min),2x24V,18Ah internal(max), or 1x24V45Ah internal(max) and1x24V 45Ah external (max) using optional battery enclosure
Charger Current: 2 x 2A temperature compensated
Serial Port: 2 x on-board RS232 connection for PC, modem, IP, or portable printer
USB Interface: 2 x USB B type connection for PC communication
Programming: On-board keypad or PC running Windows tools
Event Log: 2 x 5000 event & diagnostic + 500 fire
Networking: On-board Fault-tolerant network card (TI-002324).
Printer (optional): On-board
Enclosure/Colour: Steel IP30 /RAL7035
Cable Entry (20mm knockouts): 30 x top, 6 x rear, 3 x bottom plus 2 x double knockout rear
Approvals: EN 54-2:1998, EN 54-4:1998 & EN54-13:2005